The user can define the delayed inverse reset time characteristics with the following
formula using the set
Curve parameter D
.
t s
D
I
I
k
[ ]
=
>
−
⋅
2
1
A060817 V3 EN
(Equation 82)
t[s] Reset time (in seconds)
k
set
Time multiplier
D
set
Curve parameter D
I
Measured current
I>
set
Start value
11.2.3
Inverse-timer freezing
When the
BLOCK
input is active, the internal value of the time counter is frozen at the
value of the moment just before the freezing. Freezing of the counter value is chosen
when the user does not wish the counter value to count upwards or to be reset. This
may be the case, for example, when the inverse-time function of a protection relay
needs to be blocked to enable the definite-time operation of another protection relay
for selectivity reasons, especially if different relaying techniques (old and modern
relays) are applied.
The selected blocking mode is "Freeze timer".
The activation of the
BLOCK
input also lengthens the minimum delay
value of the timer.
Activating the
BLOCK
input alone does not affect the operation of the
START
output.
It still becomes active when the current exceeds the set
Start value
, and inactive when
the current falls below the set
Start value
and the set
Reset delay time
has expired.
Section 11
1MRS758755 A
General function block features
744
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...