![ABB RELION Series Technical Manual Download Page 312](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191312.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Operating curve type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time
Selection of time delay curve type
Operate delay time
50...200000
ms
10
50
Operate delay time
Characteristic angle
-179...180
deg
1
-90
Characteristic angle
Max forward angle
0...180
deg
1
80
Maximum phase angle in forward
direction
Max reverse angle
0...180
deg
1
80
Maximum phase angle in reverse
direction
Min forward angle
0...180
deg
1
80
Minimum phase angle in forward direction
Min reverse angle
0...180
deg
1
80
Minimum phase angle in reverse direction
Voltage start value
0.010...1.000
xUn
0.001
0.010
Voltage start value
Table 334:
DEFLPDEF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle
Operation criteria
Enable voltage limit
0=False
1=True
1=True
Enable voltage limit
Table 335:
DEFLPDEF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A
0.0086...120.0000
1
28.2000
Parameter A for customer programmable
curve
Curve parameter B
0.0000...0.7120
1
0.1217
Parameter B for customer programmable
curve
Table continues on next page
Section 4
1MRS758755 A
Protection functions
306
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...