IRIG-B time synchronization requires a COM card with an IRIG-B
input.
3.4.1.3
Signals
3.4.1.4
Settings
Table 11:
Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Time format
1=24H:MM:SS:MS
2=12H:MM:SS:MS
1=24H:MM:SS:M
S
Time format
Date format
1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
1=DD.MM.YYYY
Date format
Table 12:
Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-10
3
1=SNTP
Time synchronization source
PTP domain ID
0...255
1
0
The domain is identified by an integer, the
domainNumber, in the range of 0 to 255.
PTP priority 1
0...255
1
128
PTP priority 1, in the range of 0 to 255.
PTP priority 2
0...255
1
128
PTP priority 2, in the range of 0 to 255.
PTP announce mode
1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588 PTP announce frame mode
Table 13:
Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Date
0
Date
Time
0
Time
Local time offset
-840...840
min
1
0
Local time offset in minutes
Section 3
1MRS758755 A
Basic functions
58
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...