Table 677:
ATSABTC Output signals
Name
Type
Description
OPEN_CB1
BOOLEAN
Circuit breaker open command for bus 1
CLOSE_CB1
BOOLEAN
Circuit breaker close command for bus 1
OPEN_CB2
BOOLEAN
Circuit breaker open command for bus 2
CLOSE_CB2
BOOLEAN
Circuit breaker close command for bus 2
INPRO
BOOLEAN
Automatic operation in progress
BLKD_AL
BOOLEAN
Automatic transfer switch blocked alarm
9.5.7
Settings
Table 678:
ATSABTC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Main bus priority
1=Bus 1
2=Bus 2
1=Bus 1
Main bus priority (1 or 2)
Operate delay CB tr
0...120000
ms
10
200
Circuit breaker trip delay
Transfer dead time
0...120000
ms
10
100
Transfer dead time for closing of circuit
breaker
Reconnection delay
0...300000
ms
10
60000
Delay for opening of non prioritized CB
9.5.8
Monitored data
Table 679:
ATSABTC Monitored data
Name
Type
Values (Range)
Unit
Description
ATSABTC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.5.9
Technical data
Table 680:
ATSABTC Technical data
Characteristic
Value
Operation time accuracy
±1.0% of the set value or ±20 ms
Section 9
1MRS758755 A
Control functions
672
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...