Table 16:
Optional operation modes for setting group selection
SG operation mode
Description
Operator (Default)
Setting group can be changed with the setting
Settings/Setting group/Active group.
Value of the
SG_LOGIC_SEL
output is FALSE.
Logic mode 1
Setting group can be changed with binary inputs
(
BI_SG_2...BI_SG_6
). The highest
TRUE
binary input defines the active setting group.
Value of the
SG_LOGIC_SEL
output is TRUE.
Logic mode 2
Setting group can be changed with binary inputs
where
BI_SG_4
is used for selecting setting
groups 1-3 or 4-6.
When binary input
BI_SG_4
is
FALSE
, setting
groups 1-3 are selected with binary inputs
BI_SG_2
and
BI_SG_3
. When binary input
BI_SG_4
is
TRUE
, setting groups 4-6 are selected
with binary inputs
BI_SG_5
and
BI_SG_6
.
Value of the
SG_LOGIC_SEL
output is TRUE.
The setting group (SG) is changed whenever switching the
SG
operation mode
setting from "Operator" to either "Logic mode 1" or
"Logic mode 2." Thus, it is recommended to select the preferred
operation mode at the time of installation and commissioning and not
change it throughout the protection relay's service. Changing the
SG
operation mode
setting from "Logic mode 1" to "Logic mode 2" or
from "Logic mode 2" to "Logic mode 1" does not affect the setting
group (SG).
For example, six setting groups can be controlled with three binary inputs. The
SG
operation mode
is set to “Logic mode 2” and inputs
BI_SG_2
and
BI_SG_5
are
connected together the same way as inputs
BI_SG_3
and
BI_SG_6
.
Table 17:
SG operation mode = “Logic mode 1”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
FALSE
FALSE
1
TRUE
FALSE
FALSE
FALSE
FALSE
2
any
TRUE
FALSE
FALSE
FALSE
3
any
any
TRUE
FALSE
FALSE
4
any
any
any
TRUE
FALSE
5
any
any
any
any
TRUE
6
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
61
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...