Operating curve type
(F)PHLPTOC
PHHPTOC
(-32)=Recloser N (104)
x
(-33)=Recloser P (115)
x
(-34)=Recloser R (105)
x
(-35)=Recloser T (161)
x
(-36)=Recloser V (137)
x
(-37)=Recloser W (138)
x
(-38)=Recloser Y (120)
x
(-39)=Recloser Z (134)
x
PHIPTOC supports only definite time characteristic.
For a detailed description of timers, see the
section in this manual.
Table 205:
Reset time characteristics supported by different stages
Reset curve type
(F)PHLPTOC
PHHPTOC
Note
(1) Immediate
x
x
Available for all operate time curves
(2) Def time reset
x
x
Available for all operate time curves
(3) Inverse reset
x
x
Available only for ANSI and user
programmable curves
The
Type of reset curve
setting does not apply to PHIPTOC or when
the DT operation is selected. The reset is purely defined by the
Reset
delay time
setting.
4.1.1.7
Application
(F)PHxPTOC is used in several applications in the power system. The applications
include but are not limited to:
•
Selective overcurrent and short-circuit protection of feeders in distribution and
subtransmission systems
•
Backup overcurrent and short-circuit protection of power transformers and
generators
•
Overcurrent and short-circuit protection of various devices connected to the
power system, for example shunt capacitor banks, shunt reactors and motors
•
General backup protection
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
207
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...