IECA070698 V1 EN
Figure 209:
Three-phase current quantities during the broken conductor fault in
phase A with the ratio of negative-sequence and positive-sequence
currents
4.3.2.6
Signals
Table 402:
PDNSPTOC Input signals
Name
Type
Default
Description
I
1
SIGNAL
0
Positive sequence current
I
2
SIGNAL
0
Negative sequence current
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 403:
PDNSPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.3.2.7
Settings
Table 404:
PDNSPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
10...100
%
1
10
Start value
Operate delay time
100...30000
ms
1
100
Operate delay time
Section 4
1MRS758755 A
Protection functions
404
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...