Level detector
The residual voltage is compared to the set
Start value
. If the value exceeds the set
Start value
, the level detector sends an enable signal to the timer. The residual voltage
can be selected with the
Uo signal Sel
setting. The options are "Measured Uo" and
"Calculated Uo". If "Measured Uo" is selected, the voltage ratio for Uo-channel is
given in the global setting
Configuration/Analog inputs/Voltage (Uo,VT)
. If
"Calculated Uo" is selected, the voltage ratio is obtained from phase-voltage channels
given in the global setting
Configuration/Analog inputs/Voltage (3U,VT)
.
Example 1:
Uo is measured from the open-delta connected VTs (20/sqrt(3) kV : 100/
sqrt(3) V : 100/3 V). In this case, "Measured Uo" is selected. The nominal values for
residual voltage is obtained from the VT ratios entered in Residual voltage Uo:
Configuration/Analog inputs/Voltage (Uo,VT)
: 11.547 kV:100 V. The residual
voltage start value of 1.0 × Un corresponds to 1.0 × 11.547 kV = 11.547 kV in the
primary.
Example 2:
Uo is calculated from the phase quantities. The phase VT-ratio is 20/
sqrt(3) kV : 100/sqrt(3) V. In this case, "Calculated Uo" is selected. The nominal value
for residual voltage is obtained from the VT ratios entered in Residual voltage Uo:
Configuration/Analog inputs/Voltage (3U,VT)
: 20.000kV : 100V. The residual
voltage start value of 1.0 × Un corresponds to 1.0 × 20.000 kV = 20.000 kV in the
primary.
If "Calculated Uo" is selected, the nominal value of residual voltage is
always phase-to-phase voltage. Thus, the valid maximum setting for
residual voltage
Start value
is 0.577 × Un. The calculated Uo requires
that all three phase-to-earth voltages are connected to the protection
relay. Uo cannot be calculated from the phase-to-phase voltages.
Timer
Once activated, the timer activates the
START
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Operate delay
time
, the
OPERATE
output is activated. If the fault disappears before the module
operates, the reset timer is activated. If the reset timer reaches the value set by
Reset
delay time
, the operate timer resets and the
START
output is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is available
in the monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in
Configuration/System/
Blocking mode
which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
423
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...