Table 140:
DTMGAPC Output signals
Name
Type
Description
Q
BOOLEAN
Output status
3.16.4.7
Settings
Table 141:
DTMGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Monday Act enable
0=False
1=True
false
Activation / deactivation need on Monday
Monday Act hour
0...23
h
8
Activation hour time for Monday
Monday Act Mn
0...59
min
0
Activation minute time for Monday
Monday off delay
1...1440
min
1
60
Activation duration for Monday
Tuesday Act enable
0=False
1=True
false
Activation / deactivation need on Tuesday
Tuesday Act hour
0...23
h
8
Activation hour time for Tuesday
Tuesday Act Mn
0...59
min
0
Activation minute time for Tuesday
Tuesday off delay
1...1440
min
1
60
Activation duration for Tuesday
Wednesday Act enable
0=False
1=True
false
Activation / deactivation need on
Wednesday
Wednesday Act hour
0...23
h
8
Activation hour time for Wednesday
Wednesday Act Mn
0...59
min
0
Activation minute time for Wednesday
Wednesday off delay
1...1440
min
1
60
Activation duration for Wednesday
Thursday Act enable
0=False
1=True
false
Activation / deactivation need on
Thursday
Thursday Act hour
0...23
h
8
Activation hour time for Thursday
Thursday Act Mn
0...59
min
0
Activation minute time for Thursday
Thursday off delay
1...1440
min
1
60
Activation duration for Thursday
Friday Act enable
0=False
1=True
false
Activation / deactivation need on Friday
Friday Act hour
0...23
h
8
Activation hour time for Friday
Friday Act Mn
0...59
min
0
Activation minute time for Friday
Friday off delay
1...1440
min
1
60
Activation duration for Friday
Saturday Act enable
0=False
1=True
false
Activation / deactivation need on Saturday
Saturday Act hour
0...23
h
8
Activation hour time for Saturday
Saturday Act Mn
0...59
min
0
Activation minute time for Saturday
Saturday off delay
1...1440
min
1
60
Activation duration for Saturday
Sunday Act enable
0=False
1=True
false
Activation / deactivation need on Sunday
Table continues on next page
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
141
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...