The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value, but the
OPERATE
output is not
deactivated when blocking is activated. In the "Block all" mode, the whole function is
blocked and the timers are reset. In the "Block OPERATE output" mode, the function
operates normally but the
OPERATE
output is not activated.
4.2.5.5
Application
During an earth fault, HAEFPTOC calculates the maximum current for the current
feeder. The value is sent over an analog GOOSE to other protection relays of the
busbar in the substation. At the configuration level, all the values received over the
analog GOOSE are compared through the MAX function to find the maximum value.
The maximum value is sent back to HAEFPTOC as the
I_REF_RES
input. The
operation of HAEFPTOC is allowed in case
I_REF_RES
is lower than the locally
measured harmonics current. If
I_REF_RES
exceeds the locally measured
harmonics current, the operation of HAEFPTOC is blocked.
Analogue
GOOSE
receive
Analogue
GOOSE
receive
Analogue
GOOSE
receive
MAX
Analogue
GOOSE
send
HAEFPTOC
I_REF_RES
BLOCK
START
OPERATE
Io
I_HARM_RES
BLKD_I_REF
GUID-4F4792F0-B311-4EB2-8EC8-56F062592158 V1 EN
Figure 186:
Protection scheme based on the analog GOOSE communication
with three analog GOOSE receivers
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
357
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...