The operation of (F)DEFxPDEF can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
A070438 V3 EN
Figure 142:
Functional module diagram
Level detector
The magnitude of the operating quantity is compared to the set
Start value
and the
magnitude of the polarizing quantity is compared to the set
Voltage start value
. If both
the limits are exceeded, the level detector sends an enabling signal to the timer
module. When the
Enable voltage limit
setting is set to "False",
Voltage start value
has
no effect and the level detection is purely based on the operating quantity. If the
ENA_MULT
input is active, the
Start value
setting is multiplied by the
Start value Mult
setting.
The operating quantity (residual current) can be selected with the setting
Io signal
Sel
. The options are "Measured Io" and "Calculated Io". If "Measured Io" is selected,
the current ratio for Io-channel is given in
Configuration/Analog inputs/Current
(Io,CT)
. If "Calculated Io" is selected, the current ratio is obtained from the phase-
current channels given in
Configuration/Analog inputs/Current (3I,CT)
.
The operating quantity (residual voltage) can be selected with the setting
Uo signal
Sel.
The options are "Measured Uo" and "Calculated Uo". If "Measured Uo" is
selected, the voltage ratio for Uo-channel is given in
Configuration/Analog inputs/
Voltage (Uo,VT)
. If "Calculated Uo" is selected, the voltage ratio is obtained from the
phase-voltage channels given in
Configuration/Analog inputs/Voltage (3U,VT)
.
Example 1
: Io is measured with cable core CT (100/1 A) and Uo is measured from
open-delta connected VTs (20/sqrt(3) kV : 100/sqrt(3) V : 100/3 V). In this case,
"Measured Io" and "Measured Uo" are selected. The nominal values for residual
current and residual voltage are obtained from CT and VT ratios entered in Residual
current Io:
Configuration/Analog inputs/Current (Io,CT)
: 100 A : 1 A. The
Residual voltage Uo:
Configuration/Analog inputs/Voltage (Uo,VT)
: 11.547 kV :
100 V. The
Start value
of 1.0 × In corresponds to 1.0 * 100 A = 100 A in the primary.
The
Voltage start value
of 1.0 × Un corresponds to 1.0 * 11.547 kV = 11.547 kV in the
primary.
Section 4
1MRS758755 A
Protection functions
280
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...