3.16.2.2
Minimum pulse timer TPSGAPC
Function block
GUID-F9AACAF7-2183-4315-BE6F-CD53618009C0 V1 EN
Figure 80:
Function block
Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used for
setting the minimum pulse length for example, the signal outputs. Once the input is
activated, the output is set for a specific duration using the
Pulse time
setting. Both
timers use the same setting parameter.
GUID-8196EE39-3529-46DC-A161-B1C40224559F V1 EN
Figure 81:
A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is
longer than Pulse time setting
Signals
Table 128:
TPSGAPC Input signals
Name
Type
Default
Description
IN1
BOOLEAN
0=False
Input 1
IN2
BOOLEAN
0=False
Input 2
Table 129:
TPSGAPC Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
Table 130:
TPSGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pulse time
0...300
s
1
0
Minimum pulse time
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
135
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...