4.2.2.14
Technical revision history
Table 349:
DEFHPDEF Technical revision history
Technical revision
Change
B
Maximum value changed to 180 deg for the
Max
forward angle setting
C
Added a setting parameter for the "Measured Io"
or "Calculated Io" selection and setting parameter
for the "Measured Uo", "Calculated Uo" or "Neg.
seq. volt." selection for polarization.
Operate delay
time and Minimum operate time changed from 60
ms to 40 ms. The sector default setting values are
changed from 88 degrees to 80 degrees.
D
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting.
E
Unit added to calculated operating current output
(I_OPER).
F
Added setting
Pol quantity.
Table 350:
(F)DEFLPDEF Technical revision history
Technical revision
Change
B
Maximum value changed to 180 deg for the
Max
forward angle setting.
Start value step changed to 0.005
C
Added a setting parameter for the "Measured Io"
or "Calculated Io" selection and setting parameter
for the "Measured Uo", "Calculated Uo" or "Neg.
seq. volt." selection for polarization. The sector
default setting values are changed from 88
degrees to 80 degrees.
D
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting.
E
Unit added to calculated operating current output
(I_OPER).
F
Added setting
Pol quantity. Minimum value for
Operate delay time and Minimum operate time
changed from “60 ms” to “50 ms”. Default value for
Operate delay time and Minimum operate time
changed from “60 ms” to “50 ms”.
4.2.3
Transient/intermittent earth-fault protection INTRPTEF
4.2.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Transient/intermittent earth-fault
protection
INTRPTEF
Io> -> IEF
67NIEF
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
315
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...