"Measured Io" and "Measured Uo" are selected. The nominal values for residual
current and residual voltage are obtained from CT and VT ratios.
Residual current Io:
Configuration/Analog inputs/Current (Io, CT)
: 100 A:1 A
Residual voltage Uo:
Configuration/Analog inputs/Current (Uo, VT)
: 11.547 kV:
100 V
Residual Current start value
of 1.0 × In corresponds then 1.0 × 100 A = 100 A in
primary
Residual Voltage start value
of 1.0 × Un corresponds then 1.0 × 11.547 kV = 11.547
kV in primary
Residual Power start value
of 1.0 × Pn corresponds then 1.0 × 11.547 kV × 100 A =
1154.7kW in primary
Example 2
. Both Io and Uo are calculated from phase quantities. Phase CT-ratio is
100:1 A and Phase VT-ratio 20/sqrt(3) kV:100/sqrt(3) V. In this case "Calculated Io"
and "Calculated Uo" are selected. The nominal values for residual current and residual
voltage are obtained from CT and VT ratios entered in:
Residual current Io:
Configuration/Analog inputs/Current (3I, CT)
: 100 A:1 A
Residual voltage Uo:
Configuration/Analog inputs/Current (3U, VT)
: 20.000 kV:
100 V
Residual Current start value
of 1.0 × In corresponds then 1.0 × 100 A = 100 A in
primary
Residual Voltage start value
of 1.0 × Un corresponds then 1.0 × 20.000 kV = 20.000
kV in primary
Residual Power start value
of 1.0 × Pn corresponds then 1.0 × 20.000 kV × 100 A =
2000kW in primary
If "Calculated Uo" is selected for the
Uo signal Sel
setting, the
nominal value for residual voltage Un is always phase-to-phase
voltage. Thus, the valid maximum setting for residual
Voltage start
value
is 0.577 × Un, which corresponds to full phase-to-earth voltage
in primary.
Timer
Once activated, Timer activates the
START
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or
wattmetric IDMT. When the operation timer has reached the value of
Operate delay
time
in the DT mode or the maximum value defined by the inverse time curve, the
OPERATE
output is activated. If a drop-off situation happens, that is, a fault suddenly
disappears before the operating delay is exceeded, the timer reset state is activated.
Section 4
1MRS758755 A
Protection functions
366
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...