Inactivity timer
The module calculates the number of days the circuit breaker has remained inactive,
that is, has stayed in the same open or closed state. The calculation is done by
monitoring the states of the
POSOPEN
and
POSCLOSE
auxiliary contacts.
The inactive days
INA_DAYS
is available in the monitored data view. It is also
possible to set the initial inactive days with the
Ini inactive days
parameter.
Alarm limit check
When the inactive days exceed the limit value defined with the
Inactive Alm days
setting, the
MON_ALM
alarm is initiated. The time in hours at which this alarm is
activated can be set with the
Inactive Alm hours
parameter as coordinates of UTC. The
alarm signal
MON_ALM
can be blocked by activating the binary input
BLOCK
.
7.1.4.3
Breaker contact travel time
The Breaker contact travel time module calculates the breaker contact travel time for
the closing and opening operation. The operation of the breaker contact travel time
measurement can be described with a module diagram. All the modules in the diagram
are explained in the next sections.
A071106 V4 EN
Figure 282:
Functional module diagram for breaker contact travel time
Traveling time calculator
The travel time can be calculated using two different methods based on the setting
Travel time Clc mode
.
When the setting
Travel time Clc mode
is “From Pos to Pos”, the contact travel time
of the breaker is calculated from the time between auxiliary contacts' state change. The
opening travel time is measured between the opening of the
POSCLOSE
auxiliary
contact and the closing of the
POSOPEN
auxiliary contact. The travel time is also
measured between the opening of the
POSOPEN
auxiliary contact and the closing of
the
POSCLOSE
auxiliary contact.
Section 7
1MRS758755 A
Condition monitoring functions
538
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...