can also be used to energize an external trip relay, which in turn can be confiugred to
energize the breaker trip or close coils.
Using an external trip relay can require an external trip circuit
supervision relay. It can also require wiring a separate trip relay
contact back to the protection relay for breaker failure protection
function.
All contacts are freely programmable, except the internal fault output IRF.
3.11.1
Power output contacts
Power output contacts are normally used for energizing the breaker closing coil and
trip coil, external high burden lockout or trip relays.
3.11.1.1
Dual single-pole power outputs PO1 and PO2
Dual (series-connected) single-pole (normally open/form A) power output contacts
PO1 and PO2 are rated for continuous current of 8 A. The contacts are normally used
for closing circuit breakers and energizing high burden trip relays. They can be
arranged to trip the circuit breakers when the trip circuit supervision is not available
or when external trip circuit supervision relay is provided.
The power outputs are included in slot X100 of the power supply module.
PO1
PO2
X100
6
7
8
9
GUID-4E1E21B1-BEEC-4351-A7BE-9D2DBA451985 V1 EN
Figure 26:
Dual single-pole power output contacts PO1 and PO2
Section 3
1MRS758755 A
Basic functions
82
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...