![ABB RELION Series Technical Manual Download Page 794](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191794.webp)
Description
Type test value
Reference
Pulse magnetic field immunity
test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic
field immunity test
IEC 61000-4-10
•
2 s
100 A/m
•
1 MHz
400 transients/s
Power frequency immunity test
Binary inputs only
IEC 61000-4-16
IEC 60255-26, class A
•
Common mode
300 V rms
•
Differential mode
150 V rms
Emission tests
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 22
•
Conducted
0.15...0.50 MHz
<79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz
<73 dB (µV) quasi peak
<60 dB (µV) average
•
Radiated
30...230 MHz
<40 dB (µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz
<47 dB (µV/m) quasi peak,
measured at 10 m distance
Table 748:
Insulation tests
Description
Type test value
Reference
Dielectric tests
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
IEC 60255-27
Impulse voltage test
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
IEC 60255-27
Insulation resistance
measurements
>100 MΩ, 500 V DC
IEC 60255-27
Protective bonding resistance
<0.1 Ω, 4 A, 60 s
IEC 60255-27
Section 15
1MRS758755 A
Protection relay and functionality tests
788
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...