Level detector
The harmonics current is compared to the
Start value
setting. If the value exceeds the
value of the
Start value
setting, Level detector sends an enabling signal to the Timer
module.
Current comparison
The maximum of the harmonics currents reported by other parallel feeders in the
substation, that is, in the same busbar, is fed to the function through the
I_REF_RES
input. If the locally measured harmonics current is higher than
I_REF_RES
, the
enabling signal is sent to Timer.
If the locally measured harmonics current is lower than
I_REF_RES
, the fault is not
in that feeder. The detected situation blocks Timer internally, and simultaneously also
the
BLKD_I_REF
output is activated.
The module also supervises the communication channel validity which is reported to
the Timer.
Timer
The
START
output is activated when Level detector sends the enabling signal.
Functionality and the time characteristics depend on the selected value of the
Enable
reference use
setting.
Table 368:
Values of the Enable reference use setting
Enable reference use
Functionality
Standalone
In the standalone mode, depending on the value of the
Operating curve type setting, the time characteristics are
according to DT or IDMT. When the operation timer has
reached the value of the
Operate delay time setting in the
DT mode or the value defined by the inverse time curve,
the
OPERATE
output is activated.
Reference use
Communication
valid
When using the horizontal communication, the function is
forced to use the DT characteristics. When the operation
timer has reached the value of the
Minimum operate time
setting and simultaneously the enabling signal from the
Current comparison module is active, the
OPERATE
signal
is activated.
Communication
invalid
Function operates as in the standalone mode.
The
Enable reference use
setting forces the function to use the DT
characteristics where the operating time is set with the
Minimum
operate time
setting.
If the communication for some reason fails, the function switches to use the
Operation
curve type
setting, and if DT is selected,
Operate delay time
is used. If the IDMT curve
is selected, the time characteristics are according to the selected curve and the
Minimum operate time
setting is used for restricting too fast an operation time.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
355
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...