module has not removed the external command signal after the closing operation. To
avoid unnecessary alarms, the duration of the command signal should be set in such
a way that the maximum length of the signal is always below
Maximum Syn time
+ 5s.
Close pulse
Maximum Syn time
5s
GUID-4DF3366D-33B9-48B5-8EB4-692D98016753 V2 EN
Figure 321:
Determination of the alarm limit for a still-active command signal
Closing is permitted during
Maximum Syn time
, starting from the moment the external
command signal
CL_COMMAND
is activated. The
CL_COMMAND
input must be kept
active for the whole time that the closing conditions are waited to be fulfilled.
Otherwise, the procedure is cancelled. If the closing-command conditions are fulfilled
during
Maximum Syn time
, a closing pulse is delivered to the circuit breaker. If the
closing conditions are not fulfilled during the checking time, the alarm
CL_FAIL_AL
is activated as an indication of a failed closing attempt. The closing pulse is not
delivered if the closing conditions become valid after
Maximum Syn time
has elapsed.
The closing pulse is delivered only once for each activated external command signal,
and a new closing-command sequence cannot be started until the external command
signal is reset and reactivated. The
SYNC_INPRO
output is active when the closing-
command sequence is in progress and it is reset when the
CL_COMMAND
input is reset
or
Maximum Syn time
has elapsed.
Bypass mode
SECRSYN can be set to the bypass mode by setting the parameters
Synchrocheck
mode
and
Live dead mode
to "Off" or alternatively by activating the
BYPASS
input.
In the bypass mode, the closing conditions are always considered to be fulfilled by
SECRSYN. Otherwise, the operation is similar to the normal mode.
Voltage angle difference adjustment
In application where the power transformer is located between the voltage
measurement and the vector group connection gives phase difference to the voltages
Section 9
1MRS758755 A
Control functions
624
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...