allows the modeling of the line impedance variation in protection relay with three line
sections with independent impedance settings. This improves the accuracy of physical
fault distance conversion done in the protection relay, especially in cases where the
line impedance non-homogeneity is severe. Each section is enabled by entering a
section length, which differs from zero, to settings
Line Len section A
,
Line Len
section B
or
Line Len section C
in the order section A-> section B-> section C.
Impedance model with one line section is enabled by setting
Line Len section A
to
differ from zero. In this case the impedance settings
R1 line section A
,
X1 line section
A
,
R0 line section A
and
X0 line section A
are used for the fault distance calculation and
for conversion from reactance to physical fault distance. This option should be used
only in the case of a homogeneous line, that is, when the protected feeder consists of
only one conductor type.
Impedance model with two line sections is enabled by setting both
Line Len section A
and
Line Len section B
to differ from zero. In this case the impedance settings
R1 line
section A
,
X1 line section A
,
R0 line section A
,
X0 line section A
,
R1 line section B
,
X1
line section B
,
R0 line section B
and
X0 line section B
are used for the fault distance
calculation and for conversion from reactance to physical fault distance. This option
should be used in the case of a non-homogeneous line when the protected feeder
consists of two types of conductors.
Impedance model with three line sections is enabled by setting
Line Len section A
,
Line Len section B
and
Line Len section C
all differ from zero. In this case the
impedance settings
R1 line section A
,
X1 line section A
,
R0 line section A
,
X0 line
section A
,
R1 line section B
,
X1 line section B
,
R0 line section B
,
X0 line section B
,
R1
line section C
,
X1 line section C
,
R0 line section C
and
X0 line section C
are used for
the fault distance calculation and for conversion from reactance to physical fault
distance. This option should be used in the case of a non-homogeneous line when the
protected feeder consists of more than two types of conductors.
The effect of line impedance non-homogeneity in the conversion of fault loop
reactance into physical fault distance is demonstrated in example shown in
with 10 kilometer long feeder with three line types. The total line impedance for the
10 km line is R1 = 6.602 Ω (0.660 Ω/km) and X1 = 3.405 Ω (0.341 Ω/km), consisting
of the following sections and impedance values.
•
4 km of PAS 150 (R1 = 0.236 Ω/km, X1 = 0.276 Ω/km)
•
3 km of Al/Fe 54/9 Raven (R1 = 0.536 Ω/km, X1 = 0.369 Ω/km)
•
3 km of Al/Fe 21/4 Swan (R1 = 1.350 Ω/km, X1 = 0.398 Ω/km)
The non-homogeneity of feeder impedance can be illustrated by drawing the protected
feeder in RX-diagram (in the impedance plane), as shown in
.
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
497
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...