8.1.5.5
Monitored data
Table 578:
VMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
U12-kV
FLOAT32
0.00...4.00
xUn
Measured phase to
phase voltage amplitude
phase AB
U23-kV
FLOAT32
0.00...4.00
xUn
Measured phase to
phase voltage amplitude
phase BC
U31-kV
FLOAT32
0.00...4.00
xUn
Measured phase to
phase voltage amplitude
phase CA
BLOCK
BOOLEAN
0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
HIGH_WARN
BOOLEAN
0=False
1=True
High warning
LOW_WARN
BOOLEAN
0=False
1=True
Low warning
LOW_ALARM
BOOLEAN
0=False
1=True
Low alarm
U_INST_AB
FLOAT32
0.00...4.00
xUn
U12 Amplitude,
magnitude of
instantaneous value
U_ANGL_AB
FLOAT32
-180.00...180.00
deg
U12 angle
U_DB_AB
FLOAT32
0.00...4.00
xUn
U12 Amplitude,
magnitude of reported
value
U_DMD_AB
FLOAT32
0.00...4.00
xUn
Demand value of U12
voltage
U_RANGE_AB
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
U12 Amplitude range
U_INST_BC
FLOAT32
0.00...4.00
xUn
U23 Amplitude,
magnitude of
instantaneous value
U_ANGL_BC
FLOAT32
-180.00...180.00
deg
U23 angle
U_DB_BC
FLOAT32
0.00...4.00
xUn
U23 Amplitude,
magnitude of reported
value
U_DMD_BC
FLOAT32
0.00...4.00
xUn
Demand value of U23
voltage
U_RANGE_BC
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
U23 Amplitude range
Table continues on next page
1MRS758755 A
Section 8
Measurement functions
REC615 and RER615
567
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...