![ABB RELION Series Technical Manual Download Page 628](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191628.webp)
SECRSYN
CBXCBR
I
Closing
permission
Closing
command
GUID-A9132EDC-BFAB-47CF-BB9D-FDE87EDE5FA5 V2 EN
Figure 317:
A simplified block diagram of the Synchro check function in the
continuous mode operation
Command mode
If
Control mode
is set to "Command", the purpose of the Synchro check functionality
in the command mode is to find the instant when the voltages on both sides of the
circuit breaker are in synchronism. The conditions for synchronism are met when the
voltages on both sides of the circuit breaker have the same frequency and are in phase
with a magnitude that makes the concerned busbars or lines such that they can be
regarded as live.
In the command mode operation, an external command signal
CL_COMMAND
, besides
the normal closing conditions, is needed for delivering the closing signal. In the
command control mode operation, the Synchro check function itself closes the
breaker via the
SYNC_OK
output when the conditions are fulfilled. In this case, the
control function block delivers the command signal to close the Synchro check
function for the releasing of a closing-signal pulse to the circuit breaker. If the closing
conditions are fulfilled during a permitted check time set with
Maximum Syn time
, the
Synchro check function delivers a closing signal to the circuit breaker after the
command signal is delivered for closing.
SECRSYN
CBXCBR
I
Closing
request
Closing
command
GUID-820585ED-8AED-45B1-8FC2-2CEE7727A65C V2 EN
Figure 318:
A simplified block diagram of SECRSYN in the command mode
operation
The closing signal is delivered only once for each activated external closing command
signal. The pulse length of the delivered closing is set with the
Close pulse
setting.
Section 9
1MRS758755 A
Control functions
622
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...