9.4.6.5
Shot initiation from protection start signal
In it simplest, all auto-reclose shots are initiated by protection trips. As a result, all trip
times in the sequence are the same. This is why using protection trips may not be the
optimal solution. Using protection start signals instead of protection trips for initiating
shots shortens the trip times.
Example 1
When a two-shot-sequence is used, the start information from the protection function
is routed to the
DEL_INIT 2
input and the operate information to the
INIT_2
input.
The following conditions have to apply:
•
protection operate time = 0.5s
•
Str 2 delay shot 1
= 0.05s
•
Str 2 delay shot 2
= 60s
•
Str 2 delay shot 3
= 60s
Operation in a permanent fault:
1. Protection starts and activates the
DEL_INIT 2
input.
2. After 0.05 seconds, the first autoreclose shot is initiated. The function opens the
circuit breaker: the
OPEN_CB
output activates. The total trip time is the
protection start delay + 0.05 s the time it takes to open the circuit breaker.
3. After the first shot, the circuit breaker is reclosed and the protection starts again.
4. Because the delay of the second shot is 60 seconds, the protection is faster and
trips after the set operation time, activating the
INIT 2
input. The second shot
is initiated.
5. After the second shot, the circuit breaker is reclosed and the protection starts
again.
6. Because the delay of the second shot is 60 seconds, the protection is faster and
trips after the set operation time. No further shots are programmed after the final
trip. The function is in lockout and the sequence is considered unsuccessful.
Example 2
The delays can be used also for fast final trip. The conditions are the same as in
Example 1, with the exception of
Str 2 delay shot 3
= 0.10 seconds.
The operation in a permanent fault is the same as in Example 1, except that after the
second shot when the protection starts again,
Str 2 delay shot 3
elapses before the
protection operate time and the final trip follows. The total trip time is the protection
start delay + 0.10 s the time it takes to open the circuit breaker.
9.4.6.6
Fast trip in Switch on to fault
The
Str _ delay shot 4
parameter delays can also be used to achieve a fast and
accelerated trip with SOTF. This is done by setting the
Fourth delay in SOTF
1MRS758755 A
Section 9
Control functions
REC615 and RER615
659
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...