Operating curve type
(F)EFLPTOC
EFHPTOC
(-35)=Recloser T (161)
x
(-36)=Recloser V (137)
x
(-37)=Recloser W (138)
x
(-38)=Recloser Y (120)
x
(-39)=Recloser Z (134)
x
EFIPTOC supports only definite time characteristics.
For a detailed description of timers, see the
Table 286:
Reset time characteristics supported by different stages
Reset curve type
(F)EFLPTOC
EFHPTOC
Note
(1) Immediate
x
x
Available for all operate time curves
(2) Def time reset
x
x
Available for all operate time curves
(3) Inverse reset
x
x
Available only for ANSI and user
programmable curves
The
Type of reset curve
setting does not apply to EFIPTOC or when
the DT operation is selected. The reset is purely defined by the
Reset
delay time
setting.
4.2.1.7
Application
(F)EFxPTOC is designed for protection and clearance of earth faults in distribution
and sub-transmission networks where the neutral point is isolated or earthed via a
resonance coil or through low resistance. It also applies to solidly earthed networks
and earth-fault protection of different equipment connected to the power systems,
such as shunt capacitor bank or shunt reactors and for backup earth-fault protection of
power transformers.
Many applications require several steps using different current start levels and time
delays. (F)EFxPTOC consists of three different protection stages.
•
Low (F)EFLPTOC
•
High EFHPTOC
•
Instantaneous EFIPTOC
Section 4
1MRS758755 A
Protection functions
268
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...