L/R Control
L/R Control status
Control access
Control FB input CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850
client
2)
IEC 61850
client
3)
CTRL_REM
4)
TRUE
TRUE
3
x
CTRL_REM
FALSE
TRUE
7
x
x
CTRL_ALL
FALSE
TRUE
6
x
x
x
CTRL_ALL
4)
TRUE
TRUE
5
x
x
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.16.11.8
Signals
Table 172:
CONTROL input signals
Name
Type
Default
Description
CTRL_OFF
BOOLEAN
0
Control input OFF
CTRL_LOC
BOOLEAN
0
Control input Local
CTRL_STA
BOOLEAN
0
Control input Station
CTRL_REM
BOOLEAN
0
Control input Remote
CTRL_ALL
BOOLEAN
0
Control input All
Table 173:
CONTROL output signals
Name
Type
Description
OFF
BOOLEAN
Control output OFF
LOCAL
BOOLEAN
Control output Local
STATION
BOOLEAN
Control output Station
REMOTE
BOOLEAN
Control output Remote
ALL
BOOLEAN
Control output All
BEH_BLK
BOOLEAN
Logical device CTRL block
status
BEH_TST
BOOLEAN
Logical device CTRL test status
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
159
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...