![ABB RELION Series Technical Manual Download Page 153](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191153.webp)
3.16.7.2
Functionality
The set-reset (8 pcs) function SRGAPC is a simple SR flip-flop with a memory that
can be set or that can reset an output from the
S#
or
R#
inputs, respectively. The
function contains eight independent set-reset flip-flop latches where the
SET
input has
the higher priority over the
RESET
input. The status of each
Q#
output is retained in
the nonvolatile memory. The individual reset for each
Q#
output is available on the
LHMI or through tool via communication.
Table 151:
Truth table for SRGAPC
S#
R#
Q#
0
0
0
1)
0
1
0
1
0
1
1
1
1
1) Keep state/no change
3.16.7.3
Signals
Table 152:
SRGAPC Input signals
Name
Type
Default
Description
S1
BOOLEAN
0=False
Set Q1 output when set
R1
BOOLEAN
0=False
Resets Q1 output when set
S2
BOOLEAN
0=False
Set Q2 output when set
R2
BOOLEAN
0=False
Resets Q2 output when set
S3
BOOLEAN
0=False
Set Q3 output when set
R3
BOOLEAN
0=False
Resets Q3 output when set
S4
BOOLEAN
0=False
Set Q4 output when set
R4
BOOLEAN
0=False
Resets Q4 output when set
S5
BOOLEAN
0=False
Set Q5 output when set
R5
BOOLEAN
0=False
Resets Q5 output when set
S6
BOOLEAN
0=False
Set Q6 output when set
R6
BOOLEAN
0=False
Resets Q6 output when set
S7
BOOLEAN
0=False
Set Q7 output when set
R7
BOOLEAN
0=False
Resets Q7 output when set
S8
BOOLEAN
0=False
Set Q8 output when set
R8
BOOLEAN
0=False
Resets Q8 output when set
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
147
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...