Table 166:
Station authority level “L,R,L+R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocSta
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850 client
1)
Local
N/A
FALSE
1
x
Remote
N/A
FALSE
2
x
Local + Remote
N/A
TRUE
4
x
x
Off
N/A
FALSE
0
1) Client IEC 61850 command originator category check is not performed.
Table 167:
Station authority “L,R,L+R” using CONTROL function block
L/R Control
L/R Control status
Control access
Control FB input
CTRL.LLN0.LocSta
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850 client
1)
CTRL_OFF
N/A
FALSE
0
CTRL_LOC
N/A
FALSE
1
x
CTRL_STA
N/A
FALSE
0
CTRL_REM
N/A
FALSE
2
x
CTRL_ALL
N/A
TRUE
4
x
x
1) Client IEC 61850 command originator category check is not performed.
3.16.11.6
Station authority level “L,S,R”
Station authority level “L,S,R” adds station control access. In this level IEC 61850
command originator category validation is performed to distinguish control
commands with IEC 61850 command originator category set to “Remote” or
“Station”. There is no multilevel access.
IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
OFF
LOCAL
REMOTE
STATION
GUID-7BC51FAF-B097-4CD9-AFF4-6D1F3D548C7F V1 EN
Figure 100:
Station authority is “L,S,R”
Section 3
1MRS758755 A
Basic functions
156
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...