If the
Enable voltage limit
setting is set to "True", the magnitude of the
polarizing quantity is checked even if
Directional mode
is set to "Non-
directional" or
Allow Non Dir
to "True".
The
Characteristic angle
setting is used in the "Phase angle" mode to adjust the
operation according to the method of neutral point earthing so that in an isolated
network the
Characteristic angle
(φ
RCA
) = -90° and in a compensated network φ
RCA
= 0°. In addition, the characteristic angle can be changed via the control signal
RCA_CTL
.
RCA_CTL
affects the
Characteristic angle
setting.
The
Correction angle
setting can be used to improve selectivity due the inaccuracies
in the measurement transformers. The setting decreases the operation sector. The
correction can only be used with the "IoCos" or "IoSin" modes.
The polarity of the polarizing quantity can be reversed by setting the
Pol reversal
to
"True", which turns the polarizing quantity by 180 degrees.
For definitions of different directional earth-fault characteristics, see
the
Directional earth-fault characteristics
For definitions of different directional earth-fault characteristics,
refer to general function block features information.
The directional calculation module calculates several values which are presented in
the monitored data.
Table 319:
Monitored data values
Monitored data values
Description
FAULT_DIR
The detected direction of fault during fault
situations, that is, when
START
output is active.
DIRECTION
The momentary operating direction indication
output.
ANGLE
ANGLE_RCA
The angle difference between the operating angle
and
Characteristic angle, that is, ANGLE_RCA =
ANGLE –
Characteristic angle.
I_OPER
The current that is used for fault detection. If the
Operation mode setting is "Phase angle", "Phase
angle 80" or "Phase angle 88", I_OPER is the
measured or calculated residual current. If the
Operation mode setting is "IoSin", I_OPER is
calculated as follows I_OPER = Io x sin(ANGLE).
If the
Operation mode setting is "IoCos", I_OPER
is calculated as follows I_OPER = Io x
cos(ANGLE).
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
283
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...