4.2.3.7
Settings
Table 353:
INTRPTEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Operate delay time
40...1200000
ms
10
500
Operate delay time
Voltage start value
0.05...0.50
xUn
0.01
0.20
Voltage start value
Table 354:
INTRPTEF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Intermittent EF
2=Transient EF
1=Intermittent EF
Operation criteria
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo
Selection for used Uo signal
Table 355:
INTRPTEF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
40...60000
ms
1
500
Reset delay time
Peak counter limit
2...20
1
2
Min requirement for peak counter before
start in IEF mode
Min operate current
0.01...1.00
xIn
0.01
0.01
Minimum operating current for transient
detector
4.2.3.8
Monitored data
Table 356:
INTRPTEF Monitored data
Name
Type
Values (Range)
Unit
Description
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
INTRPTEF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
323
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...