is a risk that the fault situation in one part of the feeding system can de-energize the
whole system connected to the LV side.
GUID-1A2BD0AD-B217-46F4-A6B4-6FC6E6256EB3 V2 EN
Figure 132:
Overcurrent protection of parallel lines using directional protection
relays
(F)DPHxPDOC can be used for parallel operating transformer applications. In these
applications, there is a possibility that the fault current can also be fed from the LV-
side up to the HV-side. Therefore, the transformer is also equipped with directional
overcurrent protection.
GUID-74662396-1BAD-4AC2-ADB6-F4A8B3341860 V2 EN
Figure 133:
Overcurrent protection of parallel operating transformers
Closed ring network topology
The closed ring network topology is used in applications where electricity distribution
for the consumers is secured during network fault situations. The power is fed at least
from two directions which means that the current direction can be varied. The time
grading between the network level stages is challenging without unnecessary delays
in the time settings. In this case, it is practical to use the directional overcurrent
protection relays to achieve a selective protection scheme. Directional overcurrent
functions can be used in closed ring applications. The arrows define the operating
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
239
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...