![ABB RELION Series Technical Manual Download Page 787](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191787.webp)
Section 14
Technical data
Table 731:
Dimensions
Description
Value
Width
Frame
177 mm
Case
164 mm
Height
Frame
177 mm (4U)
Case
160 mm
Depth
201 mm (153 + 48 mm)
Weight
Complete protection relay
4.1 kg
Plug-in unit only
2.1 kg
Table 732:
Power supply
Description
Type 1
Type 2
Nominal auxiliary voltage U
n
100, 110, 120, 220, 240 V AC,
50 and 60 Hz
24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in
the auxiliary DC voltage without
resetting the relay
50 ms at U
n
Auxiliary voltage variation
38...110% of U
n
(38...264 V AC) 50...120% of U
n
(12...72 V DC)
80...120% of U
n
(38.4...300 V
DC)
Start-up threshold
19.2 V DC (24 V DC × 80%)
Burden of auxiliary voltage
supply under quiescent (P
q
)/
operating condition
DC <13.0 W (nominal)/<18.0 W
(max.)
AC <16.0 W (nominal)/<21.0 W
(max.)
DC <13.0 W (nominal)/<18.0 W
(max.)
Ripple in the DC auxiliary
voltage
Max 15% of the DC value (at frequency of 100 Hz)
Fuse type
T4A/250 V
The protection relay does not include any batteries as backup power
when the auxiliary power goes down. However, the relay
configuration and settings, events, disturbance recordings and any
critical data stay in the relay's memory because those are saved to a
nonvolatile memory. Also, the relay's real-time clock is kept running
via a 48-hour capacitor backup.
1MRS758755 A
Section 14
Technical data
REC615 and RER615
781
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...