3.14.4.2
Functionality
The GOOSERCV_INT8 function is used to connect the GOOSE 8 bit integer inputs
to the application.
3.14.4.3
Signals
Table 55:
GOOSERCV_INT8 Output signals
Name
Type
Description
OUT
INT8
Output signal
VALID
BOOLEAN
Output signal
3.14.5
GOOSERCV_INTL function block
3.14.5.1
Function block
GUID-241A36E0-1BB9-4323-989F-39668A7B1DAC V1 EN
Figure 52:
Function block
3.14.5.2
Functionality
The GOOSERCV_INTL function is used to connect the GOOSE double binary input
to the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
109
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...