Table 738:
Signal outputs and IRF output
Description
Value
1)
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
15 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
10 mA at 5 V AC/DC
1) X100: IRF,SO2
Table 739:
Double-pole power outputs with TCS function X100: PO3 and PO4
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC (two
contacts connected in a series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit monitoring (TCS)
•
Control voltage range
20...250 V AC/DC
•
Current drain through the monitoring circuit
~1.5 mA
•
Minimum voltage over the TCS contact
20 V AC/DC (15...20 V)
Table 740:
Single-pole power output relays X100: PO1 and PO2
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Section 14
1MRS758755 A
Technical data
784
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...