The operation of MAPGAPC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
AI_VALUE
OPERATE
Level
detector
Blocking
logic
BLOCK
START
Timer
ENA_ADD
t
GUID-50AA4A14-7379-43EB-8FA0-6C20C12097AC V1 EN
Figure 233:
Functional module diagram
Level detector
The level detector compares
AI_VALUE
to the
Start value
setting. The
Operation
mode
setting defines the direction of the level detector.
Table 483:
Operation mode types
Operation Mode
Description
"Under"
If the input signal
AI_VALUE
is lower than the set
value of the "Start value" setting, the level detector
enables the timer module.
"Over"
If the input signal
AI_VALUE
exceeds the set
value of the
Start value setting, the level detector
enables the timer module.
The
Absolute hysteresis
setting can be used for preventing unnecessary oscillations if
the input signal is slightly above or below the
Start value
setting. After leaving the
hysteresis area, the start condition has to be fulfilled again and it is not sufficient for
the signal to only return to the hysteresis area. If the
ENA_ADD
input is activated, the
threshold value of the internal comparator is the sum of the
Start value Add
and
Start
value
settings. The resulting threshold value for the comparator can be increased or
decreased depending on the sign and value of the
Start value Add
setting.
Timer
Once activated, the timer activates the
START
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Operate delay
time
, the
OPERATE
output is activated. If the starting condition disappears before the
module operates, the reset timer is activated. If the reset timer reaches the value set by
Reset delay time
, the operation timer resets and the
START
output is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is available
in the monitored data view.
Section 4
1MRS758755 A
Protection functions
458
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...