9.3.6
Signals
Table 655:
SECRSYN Input signals
Name
Type
Default
Description
U_BUS
SIGNAL
0
Busbar voltage
U_LINE
SIGNAL
0
Line voltage
CL_COMMAND
BOOLEAN
0=False
External closing request
BLOCK
BOOLEAN
0=False
Blocking signal of the synchro check and voltage
check function
BYPASS
BOOLEAN
0=False
Request to bypass synchronism check and voltage
check
Table 656:
SECRSYN Output signals
Name
Type
Description
SYNC_INPRO
BOOLEAN
Synchronizing in progress
SYNC_OK
BOOLEAN
Systems in synchronism
CL_FAIL_AL
BOOLEAN
CB closing failed
CMD_FAIL_AL
BOOLEAN
CB closing request failed
LLDB
BOOLEAN
Live Line, Dead Bus
LLLB
BOOLEAN
Live Line, Live Bus
DLLB
BOOLEAN
Dead Line, Live Bus
DLDB
BOOLEAN
Dead Line, Dead Bus
9.3.7
Settings
Table 657:
SECRSYN Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Live dead mode
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
1=Both Dead
Energizing check mode
Difference voltage
0.01...0.50
xUn
0.01
0.05
Maximum voltage difference limit
Difference frequency
0.0002...0.1000
xFn
0.0001
0.0010
Maximum frequency difference limit
Difference angle
5...90
deg
1
5
Maximum angle difference limit
Section 9
1MRS758755 A
Control functions
628
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...