Timer
Once activated, the Timer activates the
START
output. Depending on the value of the
set
Operating curve type
, the time characteristics are selected according to DT or
IDMT.
For a detailed description of the voltage IDMT curves, see the
curves for under voltage protection
section in this manual.
When the operation timer has reached the value set by
Operate delay time
in the DT
mode or the maximum value defined by the IDMT, the
OPERATE
output is activated.
When the user-programmable IDMT curve is selected, the operate time
characteristics are defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation occurs, that is, a fault suddenly disappears before the operate
delay is exceeded, the reset state is activated. The behavior in the drop-off situation
depends on the selected operate time characteristics. If the DT characteristics are
selected, the reset timer runs until the set
Reset delay time
value is exceeded. If the
drop-off situation exceeds the set
Reset delay time
, the Timer is reset and the
START
output is deactivated.
When the IDMT operate time curve is selected, the functionality of the Timer in the
drop-off state depends on the combination of the
Type of reset curve
,
Type of time reset
and
Reset delay time
settings.
Table 421:
Reset time functionality when IDMT operation time curve selected
Reset functionality
Setting Type of
reset curve
Setting Type of time
reset
Setting Reset delay
time
Instantaneous
reset
Operation timer is
“Reset
instantaneously”
when drop-off
occurs
“Immediate”
Setting has no
effect
Setting has no
effect
Frozen timer
Operation timer is
frozen during
drop-off
“Def time reset”
“Freeze Op timer”
Operate timer is
reset after the set
Reset delay time
has elapsed
Linear decrease
Operation timer
value linearly
decreases during
the drop-off
situation
“Def time reset”
“Decrease Op
timer”
Operate timer is
reset after the set
Reset delay time
has elapsed
Section 4
1MRS758755 A
Protection functions
416
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...