Technical data
Table 561:
SSCBR Technical data
Characteristic
Value
Current measuring accuracy
±1.5% or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0%
(at currents in the range of 10…40 × I
n
)
Operate time accuracy
±1.0% of the set value or ±20 ms
Travelling time measurement
+10 ms / -0 ms
7.1.10
Technical revision history
Table 562:
SSCBR Technical revision history
Technical revision
Change
B
Added the possibility to reset spring charge time
and breaker travel times
C
Removed the DIFTRVTOPALM and
DIFTRVTCLALM outputs and the corresponding
Open Dif alarm time and Close Dif alarm time
setting parameters
D
The
Operation cycle setting parameter renamed to
Initial CB Rmn life. The IPOW_A (_B, _C) range
changed.
E
Maximum value of initial circuit breaker remaining
life time setting (
Initial CB Rmn life) changed from
9999 to 99999. Added support for measuring
circuit breaker travelling time from opening/closing
command and auxiliary contact state signal
change.
F
Alarm Op number range increased from 9999 to
99999.
Lockout Op number setting range
increased from 9999 to 99999.
Counter initial
value setting range increased from 9999 to 99999.
Section 7
1MRS758755 A
Condition monitoring functions
552
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...