Section 11
General function block features
11.1
Definite time characteristics
11.1.1
Definite time operation
The DT mode is enabled when the
Operating curve type
setting is selected either as
"ANSI Def. Time" or "IEC Def. Time". In the DT mode, the
OPERATE
output of the
function is activated when the time calculation exceeds the set
Operate delay time
.
The user can determine the reset in the DT mode with the
Reset delay time
setting,
which provides the delayed reset property when needed.
The
Type of reset curve
setting has no effect on the reset method when
the DT mode is selected, but the reset is determined solely with the
Reset delay time
setting.
The purpose of the delayed reset is to enable fast clearance of intermittent faults, for
example self-sealing insulation faults, and severe faults which may produce high
asymmetrical fault currents that partially saturate the current transformers. It is typical
for an intermittent fault that the fault current contains so called drop-off periods,
during which the fault current falls below the set start current, including hysteresis.
Without the delayed reset function, the operate timer would reset when the current
drops off. In the same way, an apparent drop-off period of the secondary current of the
saturated current transformer can also reset the operate timer.
1MRS758755 A
Section 11
General function block features
REC615 and RER615
709
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...