Fuse failure detection criterion
Conditions and function response
Current and voltage delta function criterion
If the current and voltage delta criterion detects a
fuse failure condition, but all the voltages are not
below the
Seal in voltage setting, only the
FUSEF_U
output is activated.
If the fuse failure detection is active for more than
five seconds and at the same time all the phase
voltage values are below the set value of the
Seal
in voltage setting with Enable seal in turned to
"True", the function activates the
FUSE_3PH
output signal.
External fuse failure detection
The
MINCB_OPEN
input signal is supposed to be
connected through a protection relay binary input
to the N.C. auxiliary contact of the miniature circuit
breaker protecting the VT secondary circuit.The
MINCB_OPEN
signal sets the
FUSEF_U
output
signal to block all the voltage-related functions
when MCB is in the open state.
The
DISCON_OPEN
input signal is supposed to be
connected through a protection relay binary input
to the N.C. auxiliary contact of the line
disconnector.The
DISCON_OPEN
signal sets the
FUSEF_U
output signal to block the voltage-
related functions when the line disconnector is in
the open state.
It is recommended to always set
Enable seal in
to "True". This secures
that the blocked protection functions remain blocked until normal
voltage conditions are restored if the fuse failure has been active for 5
seconds, that is, the fuse failure outputs are deactivated when the
normal voltage conditions are restored.
The activation of the
BLOCK
input deactivates both
FUSEF_U
and
FUSEF_3PH
outputs.
6.2.5
Application
Some protection functions operate on the basis of the measured voltage value in the
protection relay point. These functions can fail if there is a fault in the measuring
circuits between the voltage transformer (or combi sensor or voltage sensor) and
protection relay.
A fault in the voltage-measuring circuit is called a fuse failure. This term is misleading
since a blown fuse is just one of the many possible reasons for a broken circuit. Since
incorrectly measured voltage can result in a faulty operation of some of the protection
functions, it is important to detect the fuse failures. A fast fuse failure detection is one
of the means to block voltage-based functions before they operate.
1MRS758755 A
Section 6
Supervision functions
REC615 and RER615
523
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...