![ABB RELION Series Technical Manual Download Page 43](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191043.webp)
PCM600 Event Viewer can be used to view the audit trail events and process related
events. Audit trail events are visible through dedicated Security events view. Since
only the administrator has the right to read audit trail, authorization must be used in
PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in LHMI/WHMI Event list
together with process related events.
To expose the audit trail events through Event list, define the
Authority logging
level parameter via
Configuration/
Authorization/Security
. This exposes audit trail events to all users.
Table 5:
Comparison of authority logging levels
Audit trail event
Authority logging level
None
Configurati
on change
Setting
group
Setting
group,
control
Settings
edit
All
Configuration change
●
●
●
●
●
Firmware change
●
●
●
●
●
Firmware change fail
●
●
●
●
●
Attached to retrofit test
case
●
●
●
●
●
Removed from retrofit
test case
●
●
●
●
●
Setting group remote
●
●
●
●
Setting group local
●
●
●
●
Control remote
●
●
●
Control local
●
●
●
Test on
●
●
●
Test off
●
●
●
Reset trips
●
●
●
Setting commit
●
●
Time change
●
View audit log
●
Login
●
Logout
●
Password change
●
Firmware reset
●
Violation local
●
Violation remote
●
1MRS758755 A
Section 2
REC615 and RER615 overview
REC615 and RER615
37
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...