The function is based on the measurement of the negative sequence current. In a fault
situation, the function starts when the negative sequence current exceeds the set limit.
The operate time characteristics can be selected to be either definite time (DT) or
inverse definite minimum time (IDMT). In the DT mode, the function operates after
a predefined operate time and resets when the fault current disappears. The IDMT
mode provides current-dependent timer characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself, if desired.
4.3.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of NSPTOC can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
A070660 V1 EN
Figure 206:
Functional module diagram
Level detector
The measured negative-sequence current is compared to the set
Start value
. If the
measured value exceeds the set
Start value
, the level detector activates the timer
module. If the
ENA_MULT
input is active, the set
Start value
is multiplied by the set
Start value Mult
.
The protection relay does not accept the
Start value
or
Start value Mult
setting if the product of the settings exceeds the
Start value
setting
range.
Timer
Once activated, the timer activates the
START
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT.
When the operation timer has reached the value of
Operate delay time
in the DT mode
or the maximum value defined by the inverse time curve, the
OPERATE
output is
activated.
Section 4
1MRS758755 A
Protection functions
396
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...