Table 309:
EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used Io signal
4.2.1.10
Monitored data
Table 310:
FEFLPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
FEFLPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 311:
EFLPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
EFLPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 312:
EFHPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
EFHPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 313:
EFIPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
EFIPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 4
1MRS758755 A
Protection functions
276
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...