3.15.7.2
Functionality
The T_TCMD function is used to convert enumerated input signal to Boolean output
signals.
Table 72:
Conversion from enumerated to Boolean
IN
RAISE
LOWER
0
FALSE
FALSE
1
FALSE
TRUE
2
TRUE
FALSE
x
FALSE
FALSE
3.15.7.3
Signals
Table 73:
T_TCMD input signals
Name
Type
Default
Description
IN
Enum
0
Input signal
Table 74:
T_TCMD output signals
Name
Type
Description
RAISE
BOOLEAN
Raise command
LOWER
BOOLEAN
Lower command
3.15.8
T_TCMD_BIN function block
3.15.8.1
Function block
GUID-A5C813D8-399A-4FBC-B1A0-E62E5C423EA5 V1 EN
Figure 63:
Function block
3.15.8.2
Functionality
The T_TCMD_BIN function is used to convert 32 bit integer input signal to Boolean
output signals.