Table 18:
SG operation mode = “Logic mode 2”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
any
any
1
TRUE
FALSE
FALSE
any
any
2
any
TRUE
FALSE
any
any
3
any
any
TRUE
FALSE
FALSE
4
any
any
TRUE
TRUE
FALSE
5
any
any
TRUE
any
TRUE
6
The setting group 1 can be copied to any other or all groups from HMI (Copy group
1).
3.6
Test mode
3.6.1
Function blocks
GUID-DFF8F71A-895C-4C06-B287-63C3CA26154C V2 EN
GUID-FA386432-3AEF-468D-B25E-D1C5BDA838E3 V3 EN
Figure 23:
Function blocks
3.6.2
Functionality
The mode of all the logical nodes in the relay's IEC 61850 data model can be set with
Test mode
.
Test mode
is selected through one common parameter via the WHMI path
Tests/IED test
. By default,
Test mode
can only be set locally through LHMI.
Test
mode
is also available via IEC 61850 communication (LD0.LLN0.Mod).
Section 3
1MRS758755 A
Basic functions
62
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...