![ABB RELION Series Technical Manual Download Page 570](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191570.webp)
Name
Type
Values (Range)
Unit
Description
LOW_ALARM
BOOLEAN
0=False
1=True
Low alarm
I_INST_A
FLOAT32
0.00...40.00
xIn
IL1 Amplitude,
magnitude of
instantaneous value
I_ANGL_A
FLOAT32
-180.00...180.00
deg
IL1 current angle
I_DB_A
FLOAT32
0.00...40.00
xIn
IL1 Amplitude,
magnitude of reported
value
I_DMD_A
FLOAT32
0.00...40.00
xIn
Demand value of IL1
current
I_RANGE_A
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
IL1 Amplitude range
I_INST_B
FLOAT32
0.00...40.00
xIn
IL2 Amplitude,
magnitude of
instantaneous value
I_ANGL_B
FLOAT32
-180.00...180.00
deg
IL2 current angle
I_DB_B
FLOAT32
0.00...40.00
xIn
IL2 Amplitude,
magnitude of reported
value
I_DMD_B
FLOAT32
0.00...40.00
xIn
Demand value of IL2
current
I_RANGE_B
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
IL2 Amplitude range
I_INST_C
FLOAT32
0.00...40.00
xIn
IL3 Amplitude,
magnitude of
instantaneous value
I_ANGL_C
FLOAT32
-180.00...180.00
deg
IL3 current angle
I_DB_C
FLOAT32
0.00...40.00
xIn
IL3 Amplitude,
magnitude of reported
value
I_DMD_C
FLOAT32
0.00...40.00
xIn
Demand value of IL3
current
I_RANGE_C
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
IL3 Amplitude range
Section 8
1MRS758755 A
Measurement functions
564
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...