![ABB RELION Series Technical Manual Download Page 557](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191557.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Life alarm level
0...99999
1
500
Alarm level for CB remaining life
Pressure alarm time
0...60000
ms
1
10
Time delay for gas pressure alarm in ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas pressure lockout in ms
Ini inactive days
0...9999
1
0
Initial value of the inactive days counter
Inactive Alm hours
0...23
h
1
0
Alarm time of the inactive days counter in
hours
7.1.8
Monitored data
Table 560:
SSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
T_TRV_OP
FLOAT32
0...60000
ms
Travel time of the CB
during opening operation
T_TRV_CL
FLOAT32
0...60000
ms
Travel time of the CB
during closing operation
T_SPR_CHR
FLOAT32
0.00...99.99
s
The charging time of the
CB spring
NO_OPR
INT32
0...99999
Number of CB operation
cycle
INA_DAYS
INT32
0...9999
The number of days CB
has been inactive
CB_LIFE_A
INT32
-99999...99999
CB Remaining life phase
A
CB_LIFE_B
INT32
-99999...99999
CB Remaining life phase
B
CB_LIFE_C
INT32
-99999...99999
CB Remaining life phase
C
IPOW_A
FLOAT32
0.000...30000.00
0
Accumulated currents
power (Iyt), phase A
IPOW_B
FLOAT32
0.000...30000.00
0
Accumulated currents
power (Iyt), phase B
IPOW_C
FLOAT32
0.000...30000.00
0
Accumulated currents
power (Iyt), phase C
SSCBR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 A
Section 7
Condition monitoring functions
REC615 and RER615
551
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...