![ABB RELION Series Technical Manual Download Page 124](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191124.webp)
Table 75:
Conversion from integer to Boolean
IN
RAISE
LOWER
0
FALSE
FALSE
1
FALSE
TRUE
2
TRUE
FALSE
x
FALSE
FALSE
3.15.8.3
Signals
Table 76:
T_TCMD_BIN input signals
Name
Type
Default
Description
IN
INT32
0
Input signal
Table 77:
T_TCMD_BIN output signals
Name
Type
Description
RAISE
BOOLEAN
Raise command
LOWER
BOOLEAN
Lower command
3.15.9
T_BIN_TCMD function block
3.15.9.1
Function block
GUID-54A013A3-E253-4A06-B033-01C7E11EC997 V1 EN
Figure 64:
Function block
3.15.9.2
Functionality
The T_BIN_TCMD function is used to convert Boolean input signals to 32 bit integer
output signals.
Table 78:
Conversion from Boolean to integer
RAISE
LOWER
OUT
FALSE
FALSE
0
FALSE
TRUE
1
TRUE
FALSE
2
Section 3
1MRS758755 A
Basic functions
118
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...