Parameter
Values (Range)
Unit
Step
Default
Description
Start value df/dt
-0.200...-0.005
xFn /s
0.005
-0.010
Setting of frequency gradient for df/dt
detection
Operate Tm Freq
80...200000
ms
10
200
Time delay to operate for under frequency
stage
Operate Tm df/dt
120...200000
ms
10
200
Time delay to operate for df/dt stage
Restore start Val
0.800...1.200
xFn
0.001
0.998
Restore frequency setting value
Restore delay time
80...200000
ms
10
300
Time delay to restore
Table 473:
LSHDPFRQ Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 474:
LSHDPFRQ Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
50
Time delay after which the definite timers
will reset
4.5.2.8
Monitored data
Table 475:
LSHDPFRQ Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Start duration
LSHDPFRQ
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.2.9
Technical data
Table 476:
LSHDPFRQ Technical data
Characteristic
Value
Operation accuracy
f<
±5 mHz
df/dt
±100 mHz/s (in range |df/dt| < 5 Hz/s)
± 2.0% of the set value (in range 5 Hz/s < |df/dt| <
15 Hz/s)
Start time
f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
Operate time accuracy
±1.0% of the set value or ±30 ms
Section 4
1MRS758755 A
Protection functions
452
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...