Table 544:
MDSOPT Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm accumulated operation time exceeds Alarm
value
WARNING
BOOLEAN
Warning accumulated operation time exceeds
Warning value
6.3.7
Settings
Table 545:
MDSOPT Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Warning value
0...299999
h
1
8000
Warning value for operation time
supervision
Alarm value
0...299999
h
1
10000
Alarm value for operation time supervision
Table 546:
MDSOPT Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Initial value
0...299999
h
1
0
Initial value for operation time supervision
Operating time hour
0...23
h
1
0
Time of day when alarm and warning will
occur
Operating time mode
1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate
Operating time mode for warning and
alarm
6.3.8
Monitored data
Table 547:
MDSOPT Monitored data
Name
Type
Values (Range)
Unit
Description
MDSOPT
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
OPR_TIME
INT32
0...299999
h
Total operation time in
hours
6.3.9
Technical data
Table 548:
MDSOPT Technical data
Description
Value
Motor runtime measurement accuracy
1)
±0.5%
1) Of the reading, for a stand-alone relay, without time synchronization
1MRS758755 A
Section 6
Supervision functions
REC615 and RER615
529
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...