Figure 124:
Configurable operating sectors
Table 239:
Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The value for DIR_A/_B/_C
The ANGLE_X is not in any of the defined sectors,
or the direction cannot be defined due too low
amplitude
0 = unknown
The ANGLE_X is in the forward sector
1 = forward
The ANGLE_X is in the reverse sector
2 = backward
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
3 = both
Table 240:
Momentary phase combined direction value for monitored data view
Criterion for phase combined direction information The value for DIRECTION
The direction information (DIR_X) for all phases is
unknown
0 = unknown
The direction information (DIR_X) for at least one
phase is forward, none being in reverse
1 = forward
The direction information (DIR_X) for at least one
phase is reverse, none being in forward
2 = backward
The direction information (DIR_X) for some phase
is forward and for some phase is reverse
3 = both
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
231
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...